文章
  • 文章
Search

语言/language

Home >> Products >>DC Contactor >>QNZ1 Series DC Contactor >> QNZ1-400A DC Contactor
Product Detail

QNZ1-400A DC Contactor

Rated operational current (A): 400 Rated operational voltage (V DC): 48 Rated insulation voltage (V DC): 1500 Coil control voltage (V): DC12/24/48/72/144 Coil operating power consumption (W): 5~7(DC24V)、4.8~7(DC48V)Coil connection method: Terminal pin / External lead Electrical life (operations): 1×10⁴ Mechanical life (operations): 10×10⁴ Mounting method: Straight plate / Bent plate Auxiliary contacts: Null

  • Product Description

1. Application

The QNZ1-A series DC contactor is suitable for use as a bypass isolation switch in frequency converters, soft starters, or other similar DC-20 loads.

2. Coding

Q N  Z   1  –   A  

1   2    3     4   5   6 

Figures

Coding

1

Enterprise Code: QN represents Nanjing Quanning Electric  Co., Ltd.

2

Z: DC Contactor

3

1: Product series

4

Basic Specification Code: the rated current (Ie)

5

A indicates normally open (NO) main contacts

6

Coil Voltage (Us)

3. Key Points

▲ Dual Contact Bridge Structure, silver alloy contacts ensure reliable contact and low contact temperature rise. ▲ High Insulation Performance, withstand voltage up to 3500V AC. ▲ Complies with the EU RoHS Environmental Directive, and meets national energy-saving and environmental protection requirements. ▲ Two Coil Connection Methods Available: fixed screw terminal or flexible lead wire. (Note: Models 600-800A are equipped with lead wire only.)

4. Operating and Installation Conditions

▲ Ambient Temperature: -40°C to +85°C ▲ Ambient Humidity: Maximum relative humidity 85% ▲ Altitude Derating: For installations above 2000 meters, derate by 5% per additional 1000 meters, up to a maximum altitude of 5000 meters. ▲ Sinusoidal Sweep Vibration at Mounting Point: 5–150Hz (5–20Hz, amplitude 25/f; 20–150Hz, amplitude 250/f²) ▲ Shock Acceleration: 30 m/s² ▲ Pollution Degree: Degree 3 ▲ Mounting Orientation: Horizontal or vertical ▲ Mounting Method: Screw mounting ▲ Applicable Duty Cycles: Continuous duty, intermittent periodic duty

5. Technical Parameters

This product series complies with the standards: IEC/EN 60947-4-1, GB/T 14048.4.

Specifications

Parameters

QNZ1-400A

Contact Configuration

1P(Normally Open

Rated Insulation Voltage Ui(V)

1500

Rated Insulation Voltage Ui(VDC)

1500

Rated Operational Voltage Ue(VDC)

48

Rated Operational Current Ie(A)DC-1

400

Contact Voltage Drop Ud(mV)

≤95

Pole Impedance Z(mΩ)

≤0.4

Minimum Load for Make

24V  200mA

Coil

Coil Voltage Us(VDC)

24、48

Pick-up Voltage(VDC)

0.85Us~1.10Us

Drop-out Voltage(VDC)

0.10Us~0.75Us

Holding Current(A)

0.21~0.28(DC24V)、0.1~0.14(DC48V)

Holding Current(W)

5~7(DC24V)、4.8~7(DC48V)

Electrical  

      Life

DC-1,Ue,Ie

    (x104 operations)

     1

DC-1, at Ue, 3Ie (Operations)

100

Operating Frequency(operations/hour)

1200

Mechanical Life (x104 operations)

10

Overload Performance(A)

1.5Ie/30min;3Ie/1min;5Ie/10s;8Ie/1s;

Operating  

Times

Pick-up Time(ms)

20~40

Release Time(ms)

5~15

Main Contact Wire or Busbar Cross-section(mm2

240

Main Contact Terminal Tightening Torque (N.m)

M10 Bolt:10.0~15.0

Insulation Resistance (MΩ)

≥30(1500VDC)

Dielectric  

 Strength

Between coil and contacts

3500V AC, 1 Min, No breakdown or flashover, leakage current ≤5mA

Between open contacts

3500V AC, 1 Min, No breakdown or flashover, leakage current ≤5mA

Temperature Rise

Coil (at Us)

≤85K

Terminals (at Ie)

≤65K

Enclosure

<60K

 Magnet

Wire

Temperature Resistance

≤180℃

Insulation Class

H级

Withstand Voltage

(Wire to ground)

1000V AC/1Min, No breakdown or flashover, leakage current ≤5mA

Weight (kg)

Approx. 0.5


6. Outline and Installation Dimensions

1760588435428297.png1760587191938552.png

QNZ1-400A Bent Bracket, Screw Terminals

1760588464532857.png1760587221752382.png

QNZ1-400A Bent Bracket, Lead Wire

1760588511809137.png1760587249915631.png

QNZ1-400A Straight Bracket, Screw Terminals


1760588541800795.png1760587279878628.png

QNZ1-400A Straight Bracket, Lead Wire


1760588573761661.png1760587310888327.png

QNZ1-400A No Bracket, Screw Terminals

1760588614357834.png1760587337597783.png

QNZ1-400A No Bracket, Lead Wire

7. Connection Diagram (Polarity must not be reversed)

                       1760587523392836.png                                                              1760587540733298.png

QNZ1-A Series(without magnetic blowout)    QNZ1-A Series(with magnetic blowout)

8. Ordering Information

When placing an order, please specify: 

■ Contactor model and name; 

■ Coil voltage; 

■ Order quantity; 

■ Special requirements;

Q N  Z   1  –   A  

1   2    3     4   5   6 

Figures

Coding

1

Enterprise Code: QN represents Nanjing Quanning Electric  Co., Ltd.

2

Z: DC Contactor

3

1: Product series

4

Basic Specification Code: the rated current (Ie)

5

A indicates normally open (NO) main contacts

6

Coil Voltage (Us)

Example:

QNZ1-200A Bent Bracket, Screw Terminals DC24V 100 units 100 units of DC contactors, one normally open main contact, 200A current, bent bracket mounting, screw terminals, coil voltage DC24V. QNZ1-400A Straight Bracket, Lead Wire 500mm DC48V 100 units 100 units of DC contactors, one normally open main contact, 400A current, straight bracket mounting, 500mm lead wire, coil voltage DC48V.

9. Precautions for Use

◆ The product coil is non-polarized; the main circuit with magnetic blowout is polarized (L1 is positive, L2 is negative), while the main circuit without magnetic blowout is non-polarized. The polarity must not be reversed, as doing so will affect the load-breaking service life. ◆ When more than one connection wire is used at the power terminal, ensure that the main power conductor is placed closest to the contactor's main circuit connection point, with the lower-current connection wires placed on top, followed by the washer, spring washer, and nut. Incorrect connection order or loose connections may cause severe overheating and lead to melting of the connected cable's insulation.

1764743581274140.jpg

◆ The tightening torque of screws and bolts used with the contactor must be controlled within the specified ranges provided below.

M3 Screw: 0.5~0.8 N.m

M3.5 Screw: 0.8~1.2 N.m

M4 Screw: 1.2~1.8 N.m

M5 Screw: 2.0~3.0 N.m

M6 Bolt: 3.0~4.5 N.m

M8 Bolt: 6.0~9.0 N.m

M10 Bolt: 10.0~15.0 N.m

M12 Bolt: 14.0~21.0 N.m


◆ Main contact wire or busbar cross-sectional area (see table).

50 Amps: 10mm²

100 Amps: 35mm²

160 Amps: 70mm²

200 Amps: 95mm²

300 Amps: 185mm²

400 Amps: 240mm²

500 Amps: 300mm²

600 Amps: 400mm²

800 Amps: 500mm²

◆ Prohibit forcibly bending the wire or busbar after installing and tightening the screws, to prevent damage to the contactor and ensure its normal operation!


This site already supports IPv6
×