QNZ1-800A DC ContactorRated operational current (A): 800 Rated operational voltage (V DC): 48 Rated insulation voltage (V DC): 1500 Coil control voltage (V): DC12/24/48/72/144 Coil operating power consumption (W): 9.8~10.8 (DC24V) , 10~13 (DC48V) Coil connection method: Terminal pin or External lead Electrical life (operations): 0.6×10⁴ Mechanical life (operations): 10×10⁴ Mounting method: Straight plate / Bent plate Auxiliary contacts: Null
1. ApplicationThe QNZ1-A series DC contactor is suitable for use as a bypass isolation switch in frequency converters, soft starters, or other similar DC-20 loads. 2. CodingQ N Z 1 – □ A □ 1 2 3 4 5 6
3. Key Points ▲ Dual Contact Bridge Structure, silver alloy contacts ensure reliable contact and low contact temperature rise. ▲ High Insulation Performance, withstand voltage up to 3500V AC. ▲ Complies with the EU RoHS Environmental Directive, and meets national energy-saving and environmental protection requirements. ▲ Two Coil Connection Methods Available: fixed screw terminal or flexible lead wire. (Note: Models 600-800A are equipped with lead wire only.) 4. Operating and Installation Conditions ▲ Ambient Temperature: -40°C to +85°C ▲ Ambient Humidity: Maximum relative humidity 85% ▲ Altitude Derating: For installations above 2000 meters, derate by 5% per additional 1000 meters, up to a maximum altitude of 5000 meters. ▲ Sinusoidal Sweep Vibration at Mounting Point: 5–150Hz (5–20Hz, amplitude 25/f; 20–150Hz, amplitude 250/f²) ▲ Shock Acceleration: 30 m/s² ▲ Pollution Degree: Degree 3 ▲ Mounting Orientation: Horizontal or vertical ▲ Mounting Method: Screw mounting ▲ Applicable Duty Cycles: Continuous duty, intermittent periodic duty 5. Technical Parameters This product series complies with the standards: IEC/EN 60947-4-1, GB/T 14048.4.
6. Outline and Installation Dimensions
QNZ1-800A Bent Bracket, Lead Wire
QNZ1-800A Straight Bracket, Lead Wire
QNZ1-800A No Bracket, Lead Wire 7. Connection Diagram (Polarity must not be reversed) QNZ1-A Series(without magnetic blowout) QNZ1-A Series(with magnetic blowout) 8. Ordering InformationWhen placing an order, please specify: ■ Contactor model and name; ■ Coil voltage; ■ Order quantity; ■ Special requirements; Q N Z 1 – □ A □ 1 2 3 4 5 6
Example: QNZ1-200A Bent Bracket, Screw Terminals DC24V 100 units 100 units of DC contactors, one normally open main contact, 200A current, bent bracket mounting, screw terminals, coil voltage DC24V. QNZ1-400A Straight Bracket, Lead Wire 500mm DC48V 100 units 100 units of DC contactors, one normally open main contact, 400A current, straight bracket mounting, 500mm lead wire, coil voltage DC48V. 9. Precautions for Use◆ The product coil is non-polarized; the main circuit with magnetic blowout is polarized (L1 is positive, L2 is negative), while the main circuit without magnetic blowout is non-polarized. The polarity must not be reversed, as doing so will affect the load-breaking service life. ◆ When more than one connection wire is used at the power terminal, ensure that the main power conductor is placed closest to the contactor's main circuit connection point, with the lower-current connection wires placed on top, followed by the washer, spring washer, and nut. Incorrect connection order or loose connections may cause severe overheating and lead to melting of the connected cable's insulation.
◆ The tightening torque of screws and bolts used with the contactor must be controlled within the specified ranges provided below.
◆ Main contact wire or busbar cross-sectional area (see table).
◆ Prohibit forcibly bending the wire or busbar after installing and tightening the screws, to prevent damage to the contactor and ensure its normal operation! |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||