文章
  • 文章
Search

语言/language

Product Detail

QNZ1-600QR Built-in Resistor Micro-power DC Contactor (Aux. Contacts Opt.)

Rated operational current (A): 600

Rated operational voltage (V DC): 60 Rated insulation voltage (V DC): 1500 Coil control voltage (V): DC24/48 Coil operating power consumption (W): 0.5 Coil connection method: Terminal pin / External lead Electrical life (operations): 2 ×10⁴ Mechanical life (operations): 20 ×10⁴ Mounting method: Straight plate / Bent plate Auxiliary contacts: Optional (11/20/02)

  • Product Description

1. Application

The QNZ1-QR series DC contactors with built-in resistor and micro-power consumption are used as bypass isolation switches in variable frequency drives, soft starters, high-frequency heating power supplies, or other similar DC-20 loads. They can also be used in circuits with a working voltage of 60V or below under DC-1 load conditions.

Compliance Standards: IEC/EN 60947-4-1, GB/T 14048.4.
Product Certifications: CCC, CE, TUV, UL, RoHS.

2.Coding

image.png

Figures

Coding

1

Enterprise Code. QN represents Nanjing Quanning Electric Co., Ltd.

2

Z: DC Contactor

3

1: Product series

4

Basic Specification Code,  the rated current Ie

5

Q indicates micro-power consumption type.

6

Model Code. Default: None, indicates standard model. X indicates X-type model.

7

Contact Configuration. Default: None, indicates one normally open main contact. B indicates one normally

closed main contact.

8

Auxiliary Contacts. Default: None. Can be added: F11 (one NO, one NC), F20 (two NO), F02 (two NC).

9

Coil Voltage Us

10

Product Code. Default: R. RR indicates with built-in buffer resistor.

3. Key Points

▲ Built-in buffer resistor structure eliminates the need for installing additional charging resistors, saving customer cost while maintaining virtually the same space and volume. ▲ Coil with micro-power consumption technology, featuring high efficiency, energy saving, and surge protection. The coil itself does not generate heat. ▲ Strong resistance to shock and vibration. High contact pressure, silver alloy contacts ensure reliable connection, low contact temperature rise, and strong overload capacity. ▲ Rare earth strong magnetic arc extinguishing, long electrical lifespan, strong anti-welding performance, safe and reliable. ▲ High insulation performance, withstands 3500V power frequency voltage. ▲ Complies with EU RoHS environmental directive and national energy-saving and environmental protection requirements. ▲ Two coil connection options: Fixed terminal block method and flexible lead wire method. *(Note: 600-1200QR models are only available with lead wires).

4. Operating and Installation Conditions

▲ Ambient Temperature: -40°C to +85°C. ▲ Ambient Humidity: Maximum relative humidity 85%. ▲ When the installation site altitude exceeds 2000 meters, derate by 5% for every additional 1000 meters. Maximum altitude should not exceed 5000 meters. ▲ Sinusoidal sweep frequency vibration at the mounting point: 10–500 Hz (Frequency 10–50 Hz, Amplitude 2.5mm; 50–200 Hz, Amplitude 0.16mm; 200–500 Hz, Acceleration 50 m/s²). ▲ Pollution Degree: Pollution Degree 3. ▲ Installation Orientation: Horizontal or vertical. ▲ Mounting Method: Screw mounting. ▲ Applicable Duty Cycle: Uninterrupted duty, Intermittent periodic duty.

5. Technical Parameters

This series complies with standards: IEC/EN 60947-4-1, GB/T 14048.4.

Specifications

Parameters

QNZ1-600QR

Contact Configuration

1P (Normally Open); 1P (Normally Open)

Rated Insulation Voltage Ui (V)

1500

Bypass Operating Voltage Un (VDC)

1500

Rated Operational Voltage Ue (VDC)

60

Rated Operational Current Ie (A) DC-1

600

Contact Voltage Drop Ud (mV)

≤95

Polar Impedance Z (mΩ)

≤0.4

Buffer Resistor R (Ω)

8

Resistor Engagement Frequency

Under DC780V, engagement interval ≥10min

Min. Connectable Load

24V  200mA

Auxiliary Contact Parameters

Ith: 10A; DC-12: Ue/Ie: 24V/10A; DC-12: Ue/Ie: 48V/4A; DC-12: Ue/Ie: 220V/1A.

Control Coil

Coil Voltage Us (VDC)

24, 48

Pick-up Voltage (VDC)

0.85Us to 1.10Us

Drop-out Voltage (VDC)

0.10Us to 0.75Us

Pick-up Current (A)

0.5–1.5, see appendix for details

Holding Current (A)

0.001–0.05, see appendix for details

Pick-up Power (W)

30–40, see appendix for details

Holding Power (W)

0.5, see appendix for details

Recommended Power Supply

Switching power supply; PWM modulated power supply with 100% duty cycle; Rectifier-filtered

power supply with ripple factor <5%

Optional Power Supply

(Customized)

DC square wave power supply; Rectifier-filtered power supply with ripple factor >5%

Electrical Life

DC-1, Ue, Ie (10k operations)

2

Operating Frequency (operations/hour)

300 (1 operation every 12 seconds, on/off interval not less than 0.5s)

Mechanical Life (10k operations)

20

Overload Performance (A)

1.5Ie/30min; 3Ie/1min; 5Ie/10s; 8Ie/1s; other data refer to overload curve graphs

Operate Time

Pick-up Time (ms)

600

Drop-out Time (ms)

50

Main Contact Wire or Busbar Cross-sectional Area (mm²)

400

Main Contact Terminal Tightening Torque (N.m)

M12 bolt: 14.0–21.0

Insulation Resistance (MΩ)

≥5 (500VDC)

Dielectric

Strength

Between Coil and Contacts

AC 3500V/1Min, no breakdown or flashover, leakage current ≤5mA

Between Open Contacts

AC 3500V/1Min, no breakdown or flashover, leakage current ≤5mA

Temperature Rise

Coil (at Us)

≤15K

Terminal (at Ie)

≤65K

Housing

<60K

Enameled Wire

Temperature Resistance

≤180℃

Insulation Class

Class H

Dielectric Strength

(Enamel to Ground)

AC 1000V/1Min, no breakdown or flashover, leakage current ≤5mA

Weight (kg)

Approx. 0.9

Appendix: Coil Parameters

Coil Voltage (VDC)

Starting Current (A)

Holding Current (A)

Pick-up Power (W)

Holding Power (W)

24

≤1.5

≤0.02

≤36

≤0.48

48

≤1

≤0.01

≤48

≤0.48

QNZ-QR Overload Current vs Time Curves:

1765422454267949.jpg

6. Outline and Mounting Dimensions (Same for NO and NC Types)

image.pngimage.pngimage.png

      600QR Bent Plate - Lead Wire                  600QR Straight Plate - Lead Wire                    600QR No Plate - Lead Wire     

image.pngimage.pngimage.png

600QRR Bent Plate - Lead Wire                  600QRR Straight Plate - Lead Wire                    600QRR  No Plate - Lead Wire


image.pngimage.pngimage.png


 600QFR Bent Plate - Lead Wire                  600QFR Straight Plate - Lead Wire                    600QFR  No Plate - Lead Wire

image.pngimage.pngimage.png

600QFRR Bent Plate - Lead Wire                  600QFRR Straight Plate - Lead Wire                    600QFRR  No Plate - Lead Wire


1761016630597340.png



QNZ1-600QR Bent Plate Outline and Mounting Dimensions


1761016660718671.png



QNZ1-600QR Straight Plate Outline and Mounting Dimensions


1761016695252749.png



QNZ1-600QR No Plate Outline and Mounting Dimensions


1761016829926219.png


QNZ1-600QRR Bent Plate Outline and Mounting Dimensions


1761016873225146.png



QNZ1-600QRR Straight Plate Outline and Mounting Dimensions


1761016902319196.png



QNZ1-600QRR No Plate Outline and Mounting Dimensions


1761017510209154.png



QNZ1-600QFR Bent Plate Outline and Mounting Dimensions


1761017538576616.png



QNZ1-600QFR Straight Plate Outline and Mounting Dimensions


1761017579173025.png



QNZ1-600QFR Straight Plate Outline and Mounting Dimensions


1761017718441855.png



QNZ1-800QFR/1000QFR/1200QFR No Plate Outline and Mounting Dimensions


1761017766958365.png



QNZ1-600QFRR Bent Plate Outline and Mounting Dimensions


1761017807749819.png


QNZ1-600QFRR Straight Plate Outline and Mounting Dimensions


1761017845256727.png


QNZ1-600QFRR No Plate Outline and Mounting Dimensions

7. Wiring Diagram (Positive and Negative Poles Must NOT Be Reversed)

1761018078652824.png

QNZ1-QR                   QNZ1-QRR

8. Ordering Information

When placing an order, please specify:        ■ Contactor model and name;        ■ Coil voltage;        ■ Order quantity;        ■ Special requirements; 


image.png

Figures

Coding

1

Enterprise Code. QN represents Nanjing Quanning Electric Co., Ltd.

2

Z: DC Contactor

3

1: Product series

4

Basic Specification Code,  the rated current Ie

5

Q indicates micro-power consumption type.

6

Model Code. Default: None, indicates standard model. X indicates X-type model.

7

Contact Configuration. Default: None, indicates one normally open main contact. B indicates one normally

closed main contact.

8

Auxiliary Contacts. Default: None. Can be added: F11 (one NO, one NC), F20 (two NO), F02 (two NC).

9

Coil Voltage Us

10

Product Code. Default: R. RR indicates with built-in buffer resistor.

Examples:QNZ1-200QRR DC24V Bent Plate Lead Wire 100 units; Meaning: 100 units of DC contactor with built-in buffer resistor and micro-power consumption, current 200A, with resistor, with bent mounting plate, with lead wires, coil voltage DC24V. QNZ1-400QR DC48V Straight Plate Terminal Block 100 units; Meaning: 100 units of DC contactor with micro-power consumption, without resistor, with straight mounting plate, with terminal blocks, current 400A, coil voltage DC48V. QNZ1-600QXR DC48V No Plate Terminal Block 100 units; Meaning: 100 units of DC contactor with micro-power consumption, X-type, without resistor, without mounting plate, with terminal blocks, current 600A, coil voltage DC48V.

9. Usage Precautions

WARNING:     ◆ The product coil is polarized. If connected in reverse, the contactor will not operate. The main circuit with magnetic blowout is polarized (L1 is positive, L2 is negative); without magnetic blowout, it is non-polarized. The positive and negative poles must NOT be reversed, as reversal can affect the load-breaking lifespan.     ◆ The energy-saving coil has a relatively large starting current at initial operation, lasting between 100–120ms depending on the product's characteristics. Therefore, the driving power for the contactor must be greater than the coil power, and the operating frequency must not exceed the rated value. Otherwise, it may affect the normal starting of the DC contactor or even burn out the energy-saving module, rendering the contactor inoperative.     ◆ The product has a built-in coil energy-saving module; no additional PWM or other energy-saving modules are required. If PWM pulse signals are still used to control the coil, the PWM output voltage must be set to 100%, otherwise it may affect the reliable operation of our contactors. Step-type power supply mode is recommended.     ◆ When using more than one connection wire at a power terminal, ensure the main power wire is closest to the contactor's main circuit connection point, followed by smaller current wires on top, then the washer, spring washer, and nut. Incorrect connection order or loose connections can cause severe overheating and melt the cable insulation.

1764743581274140.jpg

   

    ◆ The tightening torque for screws and bolts used with the contactor should be controlled within the specified ranges below .

M3 Screw: 0.5~0.8 N.m

M3.5 Screw: 0.8~1.2 N.m

M4 Screw: 1.2~1.8 N.m

M5 Screw: 2.0~3.0 N.m

M6 Bolt: 3.0~4.5 N.m

M8 Bolt: 6.0~9.0 N.m

M10 Bolt: 10.0~15.0 N.m

M12 Bolt: 14.0~21.0 N.m


    ◆ Main contact wire or busbar cross-sectional area .

50 Amps: 10mm²

100 Amps: 35mm²

160 Amps: 70mm²

200 Amps: 95mm²

300 Amps: 185mm²

400 Amps: 240mm²

500 Amps: 300mm²

600 Amps: 400mm²

800 Amps: 500mm²

1000 Amps: 600mm²

1200 Amps: 800mm²


    ◆ Do NOT forcibly bend wires or busbars after tightening the product's mounting screws, to prevent damage to the contactor and ensure its normal use.


This site already supports IPv6
×
seo seo