文章
  • 文章
Search

语言/language

Home >> Products >>Relays >>QNJ-C Series Zero-Power Magnetic Latching DC Relay >> QNJ-100C Zero-Power Magnetic Latching DC Relay
Product Detail

QNJ-100C Zero-Power Magnetic Latching DC Relay

Rated operational current (A): 100 Rated operational voltage (V DC): 60 Rated insulation voltage (V DC): 1500 Coil control voltage (V): DC12/24 Coil operating power consumption (W): 0 Coil connection method: Plug-in Electrical life (operations): 1×10⁴ Mechanical life (operations): 20×10⁴ Auxiliary contacts: Null

  • Product Description

1. Application

The QNJ-C series zero-power magnetic latching DC relays are mainly used in energy storage,charging equipment, etc. Product complies with standards: IEC/EN 60947-4-1, GB/T 14048.4. Product certification: RoHS.

2.Coding

QN J –  C 

1  2    3  4  5

Figures

Coding

1

Company code: QN represents Nanjing Quanning Electric Co., Ltd.

2

J: DC Relay

3

Basic Specification Code: the rated current Ie

4

C indicates magnetic latching energy-saving coil

5

Coil Voltage (Us)

3.Key Points

Zero-power bistable magnetic latching energy-saving coil, with no self-heating of the coil;▲ High insulation performance, withstand voltage 3500V AC at power frequency; ▲ Complies with EU RoHS environmental directive and national energy-saving and environmental protection requirements.

4. Operating and Mounting Conditions

▲ Ambient temperature: -40°C to +85°C; ▲ Ambient humidity: Maximum relative humidity 85%; ▲ For installations above 2000m altitude, derate by 5% per 1000m increment, maximum altitude not exceeding 5000m; ▲ Sinusoidal sweep vibration frequency at mounting point: 10 ~ 500Hz (Frequency 10Hz~50Hz, amplitude 2.5mm; 50Hz~200Hz, amplitude 0.16mm; 200Hz~500Hz, acceleration 50 m/s²); ▲ Shock acceleration: 300 m/s²; ▲ Pollution degree: Degree 3; ▲ Applicable duty types: Uninterrupted duty, intermittent periodic duty.

5. Technical Parameters

This product series complies with standards: IEC/EN 60947-4-1, GB/T 14048.4.

Specifications

Parameters

QNJ-100C

Contact Configuration

1P (Normally Open)

Rated insulation voltage Ui (V)

1500

Bypass operating voltage Un (V DC)

1500

Rated operational voltage Ue (V DC)

60

Rated operational current Ie (A) DC-1

100

Contact voltage drop Ud (mV)

≤60

Polar impedance Z (mΩ)

≤0.4

Minimum make load

24V  200mA

Control Coil

Coil voltage Us (V DC)

12、24

Pick-up voltage (V DC)

0.85Us ~ 1.10Us (Coil A1 or red wire to positive, A2 or black wire to negative)

Drop-out voltage (V DC)

0.85Us ~ 1.10Us (Coil A1 or red wire to positive, A2 or black wire to negative)

Pick-up current (A)

≤2 (12V), ≤1 (24V) (coil energization time 50ms~120ms)

Hold current (A)

0

Pick-up power (W)

≤36 (coil energization time 50ms~120ms)

Hold power (W)

0

Electrical life

DC-1, Ue, Ie (10⁴ operations)

1

Operating rate (ops/h)

300 (1 operation per 12 seconds, ON/OFF interval not less than 0.5s)

Mechanical life (10⁴ operations)

20

Overload performance (A)

1.5Ie/30min;3Ie/1min;5Ie/10s;8Ie/1s;

Operating time

Pick-up time (ms)

20 ~ 40

Release time (ms)

10 ~ 30

Main contact wire/busbar cross-section (mm²)

35

nsulation resistance (MΩ)

≥5(500VDC)

Dielectric strength

Between coil and contacts

AC 3500V / 1 Min, no breakdown or flashover, leakage current ≤5mA

Between open contacts

AC 3500V / 1 Min, no breakdown or flashover, leakage current ≤5mA

Temperature rise

Coil (at Us)

≤15K

Terminals (at Ie)

≤65K

Housing

<60K

Enameled wire

Temperature resistance

≤180℃

Insulation class

Class H

Withstand voltage

(enamel to ground)

1000V / 1 Min, no breakdown or flashover, leakage current ≤5mA

Weight (kg)

Approx. 0.14


6. Outline and Mounting Dimensions

image.png1760923811658483.png


QNJ-100C Outline and Mounting Dimensions

7. Wiring Diagram

1760924144591853.png

QNJ-C


8. Ordering Information

Please specify the following when ordering: ■ Relay model and name; ■ Coil voltage; ■ Order quantity; ■ Special requirements.

QN  J –   C  

1   2    3   4   5

Figures

Coding

1

Company code: QN represents Nanjing Quanning Electric Co., Ltd.

2

J: DC Relay

3

Basic Specification Code: the rated current Ie

4

C indicates magnetic latching energy-saving coil

5

Coil Voltage (Us)

Example: QNJ-200C DC24V, 100 units;

This indicates 100 units of zero-power magnetic latching DC relay, main contact 1NO, current 200A, coil voltage DC24V.

9. Usage Precautions

◆ The relay coil is polarized (A1 is positive, A2 is negative); the main circuit is non-polarized. ◆ The bistable magnetic latching energy-saving coil has a relatively high inrush current during the initial make/break operation, lasting between 50ms~120ms depending on the product's characteristics. Therefore, the driver power supply must exceed the coil power rating, and the operating frequency must not exceed the rated value. Otherwise, it may affect the normal startup of the DC relay 'or' even burn out the coil, rendering the relay inoperable. ◆ The magnetic latching DC relay uses a square wave pulse power supply mode. The magnetic latching coil must not be continuously energized. Make: Connect coil A1 'or' red wire to positive, A2 'or' black wire to negative. Break: Connect coil A1 'or' red wire to negative, A2 'or' black wire to positive. ◆ Main contact wire 'or' busbar cross-section (see table below):

100 Amps: 35mm²

160 Amps: 70mm²

200 Amps: 95mm²

300 Amps: 185mm²

400 Amps: 240mm²

450 Amps: 300mm²


This site already supports IPv6
×