QNC-630(B)04 44WH Arc-less AC ContactorRated Load Voltage (VAC): 690 Rated Load Current (A): 630 Rated Insulation Voltage (V): 1500 Coil Control Voltage (V):48, 110, 220, AC380V 50/60Hz AC/DC220~380V (Wide voltage 132~540V) AC/DC48~127V (Wide voltage 28~190V) Coil Operating Power Consumption (W): ≤2 Electrical Life (Operations): 150 × 10⁴ Mechanical Life (Operations): 150 × 10⁴ Contact Configuration: NO or NC (B indicates Normally Closed) Auxiliary Contacts: 4NO+4NC
1. ApplicationThe QNC-WH Series Arc-less AC contactors are suitable for circuits with a working voltage up to 1500V at AC-3 utilization category under 50Hz (or 60Hz) AC. They are used for remote connection and disconnection of circuits and frequent starting control of AC motors. Products comply with standards: IEC/EN 60947-4-1, GB/T 14048.4. Products certified: RoHS. 2.Coding
3. Key Points▲ Arc-less make/break technology for main contacts, long electrical life, strong anti-welding performance, safe and reliable. ▲ Micro-power consumption DC coil technology, featuring high efficiency, energy savings, and surge protection; coil itself does not generate heat. ▲ Strong resistance to shock and vibration, high contact pressure, silver alloy contacts, reliable contact, low contact temperature rise, strong overload capability. ▲ Coil adopts AC/DC integrated design scheme, avoiding AC/DC conversion, saving customer usage costs. ▲ High insulation performance, power frequency withstand voltage 3500V. ▲ Complies with EU RoHS environmental directive, meets national energy-saving and environmental protection requirements. 4. Operating and Installation Conditions▲ Ambient temperature: -40°C to +85°C. ▲ Ambient humidity: Maximum relative humidity 85%. ▲ When installation altitude exceeds 2000 meters, derate by 5% per 1000 meters increase, maximum not exceeding 5000 meters. ▲ Sinusoidal sweep vibration frequency at mounting point: 10~500Hz (frequency 10Hz~50Hz, amplitude 2.5mm; 50Hz~200Hz, amplitude 0.16mm; 200Hz~500Hz, acceleration 50m/s²). ▲ Shock acceleration: 300m/s². ▲ Pollution degree: Pollution degree 3. ▲ Mounting orientation: Horizontal or vertical. ▲ Mounting method: Screw mounting. ▲ Applicable duty cycle: Uninterrupted duty, intermittent periodic duty. 5. Technical ParametersThis series complies with standards: IEC/EN 60947-4-1, GB/T 14048.4.
Attached Tables: Four-pole Contactor Coil Parameters:
QNC-WH Overload Current vs. Time Curves:
6. Outline and Installation Dimensions (Dimensions are the same for Normally Open and Normally Closed Models)
QNC-630 0444 WH Outline and Installation Dimensions 7. Wiring Diagrams
QNC-0444 WH
QNC-B0444 WH 8. Ordering InformationWhen placing an order, please specify: ■ Contactor model and name; ■ Coil voltage; ■ Order quantity; ■ Special requirements;
Examples:QNC-50033 AC220V WH 100 units; 100 units of three-pole arc-less AC contactors, three normally open main contacts, 500A current, auxiliary contacts three-NO-three-NC, coil voltage AC220V. QNC-10000444 AC220V WH 100 units; 100 units of four-pole arc-less AC contactors, four normally open main contacts, 1000A current, auxiliary contacts four-NO-four-NC, coil voltage AC220V. 9. Precautions for Use◆ If the product coil input is DC voltage, then the coil has polarity (A1 is positive, A2 is negative). ◆ The energy-saving coil has a relatively large starting current at initial operation, lasting between 100~120ms depending on the product's own characteristics. Therefore, the driving power for the contactor must be greater than the coil power of the product, and the operating frequency must not exceed the rated value. Otherwise, it may affect the normal startup of the contactor, or even burn out the energy-saving module, causing the contactor to fail. ◆ The product has a built-in coil energy-saving module; no additional PWM or other energy-saving modules are required. If PWM pulse signals are still used to control the contactor coil, the PWM output voltage must be adjusted to 100%; otherwise, it may affect the reliable operation of our contactors. A step-type power supply mode is recommended. ◆ When using more than one connection wire at the power terminal, ensure the main power wire is closest to the main circuit connection point of the contactor, with the smaller current connection wire on top, followed by the washer, spring washer, and nut. Incorrect connection order or poor connection may cause severe overheating and melt the insulation of the connecting cable.
◆ Contactor Communication Function Introduction: The QNC-WH arc-less contactor is an electrical control device integrating remote control, status monitoring, and intelligent linkage. It supports interaction with IoT platforms, local servers, or mobile terminals via wired or wireless communication protocols to achieve intelligent management of electrical loads. Wired Protocol: RS-485 (Modbus RTU). Remote Control: Delay and make/break functions can be controlled by sending commands via MQTT/HTTP API. Status Reporting: Real-time upload of parameters (voltage, current, temperature, switch status) to the cloud, default interval 5 seconds (customizable). Parameter Setting: Real-time setting of overcurrent, overvoltage, delay, working mode, etc. (customizable).
◆ The tightening torque for screws and bolts used with the contactor should be controlled within the specified ranges below (see table).
◆ Main contact wire or busbar cross-sectional area (see table).
◆ It is prohibited to forcibly bend the wires or busbars after installing and tightening the screws, as this may damage the contactor! |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||